X-VOLT ® RHZ1-OL, AL - 18/30 (36) kV

Application

X-VOLT® RHZ1-OL, AL is used for medium voltage installations or distribution networks both indoors and outdoors.
Ex. for the supply of transformer stations, infrastructure, wind turbines, solar parks, factory plants, data centers along with others. 

Construction

Conductor

Aluminium, class 2 

Insulation

XLPE. Semiconducting layer around the isolation. Easy strippable

Screen

Screen of Cu threads and Cu tape

Outer sheath

Halogen free polyolefine type DMZ1 acc. to 620-1 and type ST7 acc. to IEC 60502-2, red

Comments

Optional: Hygroscopic tape is made to achieve longitudinal watertightness on the conductor, type X-VOLT RHZ1-2OL

Technical data

Working temperature

-15° C to +90° C

Rated voltage

18/30 (36) kV (Uo/U (Um))

Bend radius

15 x cable diameter

Technical comments

Short circuit temp.: max 250° C / 5 sec.

Approvals

IEC 60754-1, IEC 60228, IEC 60502-2, UNE 211605, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
For industrial use
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
10401095.W 5704403061082 1x95/16 280 Drum 33,1 1080
10401120.W 5704403174478 1x120/16 324 Drum 34,8 1205
10401150.W 5704403174485 1x150/16 368 Drum 36,5 1325
10401150.H25.W 5704403174492 1x150/25 368 Drum 36,7 1410
10401185.W 5704403174508 1x185/16 424 Drum 37,9 1485
10401240.W 5704403063680 1x240/16 502 Drum 40,7 1735
10401300.W 5704403174515 1x300/16 577 Drum 42,9 1950
10401300.H25.W 5704403067510 1x300/25 577 Drum 43,0 2030
10401400.W 5704403063697 1x400/16 673 Drum 46,0 2320
10401500.W 5704403174522 1x500/16 777 Drum 50,1 2720
10401630.W 5704403174539 1x630/16 895 Drum 53,1 3220
* The values can have small deviations