(N)HXCH-FE 180/E30 - 0.6/1 kV

Application

(N)HXCH-FE 180/E30 is suitable for fixed installation, which there is a requirement for power supply during a fire for up to 3 hours (750° C) such as generators, UPS systems or emergency and panic lighting.

Construction

Conductor

Bare Cu, solid or stranded

Insulation

Micatape

Conductor color

According to CENELEC HD 308 S2 and VDE 0293

Filling sheath

Halogen free compound

Outer sheath

Polyolefin compound according to CENELEC HD 604 S1 and VDE 0276-604 “HM4”, orange

Technical data

Working temperature

+90º C

Rated voltage

0.6/1 kV

Test voltage

4000 V, 50 Hz

Approvals

IEC 60332-3, IEC 60331, IEC 60754, IEC 61034, CE, RoHS
Environmentally friendly
Fire retardant acc. to IEC 60332-3
Flame retardant acc. to IEC 60332-1
For emergency circuits
For use in homes
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Low smoke emission during fire acc. to 61034
Low voltage cable
Max. working temp. +90° C
Operation secured acc. to IEC 60331
Suited for public places
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
69104006 5704403061570 4x6/6 53 D./Cut 16,9 522
69104010 5704403018628 4x10/10 73 D./Cut 18,9 746
69104016 5704403026562 4x16/16 97 D./Cut 21,9 1119
69104025 5704403027743 4x25/16 135 D./Cut 26,9 1583
69104035 5704403028689 4x35/16 165 D./Cut 29,9 2002
69104050 5704403033775 4x50/25 201 D./Cut 33,9 2700
69104070 5704403033799 4x70/35 255 D./Cut 38,9 3838
69104095 5704403033768 4x95/50 314 D./Cut 42,9 5181
69104120 5704403033782 4x120/70 364 D./Cut 46,9 6500
69104150 5704403033805 4x150/70 416 D./Cut 52,9 7950
69104185 5704403033812 4x185/95 480 D./Cut 58,9 10130
69104240 5704403041251 4x240/120 565 D./Cut 64,9 13190
* The values can have small deviations